| Technical Data |
| Inputs |
| Number: |
4 voltage and current (3 phases + neutral) |
| Maximum voltage: |
1000 Vrms (6 kV peak) |
| Maximum sampling speed: |
200 kS/s on each channel simultaneously |
| Volt/Amps/Hertz |
| Vrms (AC + DC) Measurement range: |
1 … 1000 V |
| Accuracy: |
0.1% of Vnom |
| Vpeak Measurement range: |
1 … 1400 V |
| Accuracy: |
5% of Vnom |
| Crest factor, voltage Measurement range: |
1.0 … > 2.8 |
| Accuracy: |
±5% |
| Arms (AC + DC) Measurement range: |
0 … 20 kA |
| Accuracy: |
±0.5% ± 5 counts |
| Apeak Measurement range: |
0 … 5.5 kA |
| Accuracy: |
5% |
| Crest factor, A Measurement range: |
1 … 10 |
| Accuracy: |
±5% |
| Hz 50 Hz nominal Measurement range: |
40 … 70 Hz |
| Accuracy: |
±0.01 Hz |
| Dips and swells |
| Vrms (AC+DC) 2Measurement range: |
0.0% … 100% of Vnom |
| Accuracy: |
±0.2% of nominal voltage |
| Arms (AC+DC) ? Measurement range: |
0 …. 20 kA |
| Accuracy: |
±1% … ± counts |
| Harmonics |
| Harmonic (interharmonic) (n) Measurement range: |
DC, 1..50; (Off, 1..49) measured according to IEC 61000-4-7 |
| Vrms Measurement range: |
0.0 … 1000 V |
| Accuracy: |
±0.05% of nominal voltage |
| Arms Measurement range: |
0.0 ± 4000 mV x clamp scaling |
| Accuracy: |
±5% ± 5 counts |
| Watts Measurement range: |
Depends on clamp scaling and voltage |
| Accuracy: |
±5% ± n x 2% or reading, ± 10 counts |
| DC voltage Measurement range: |
0.0 ± 1000 V |
| Accuracy: |
±0.2% of nominal voltage |
| THD Measurement range: |
0.0 … 100.0% |
| Accuracy: |
±2.5% V and A (± 5% Watt) |
| Hz Measurement range: |
0 … 3500 Hz |
| Accuracy: |
± 1 Hz |
| Phase angle Measurement range: |
-360° … +360° |
| Accuracy: |
± n x 1.5° |